CISA Lists Three Danfoss AK-SM 800A Flaws as Exploited, With a Nov. 28 Deadline for Two
Security / news
CISA Lists Three Danfoss AK-SM 800A Flaws as Exploited, With a Nov. 28 Deadline for Two
The refrigeration controllers' ICS advisory said no exploitation had been reported on Nov. 18; the catalog entry came seven days later.

Three flaws in Danfoss AK-SM 800A Series refrigeration controllers joined CISA's Known Exploited Vulnerabilities catalog on November 25, 2026, which means CISA has evidence that attackers are using them. Two of the three, CVE-2023-25914 and CVE-2023-25915, require valid credentials and carry a federal patch deadline of November 28, three days after listing. The third, CVE-2025-41450, needs none, and its deadline is December 9.
CISA's catalog entry was part of a batch of 10 additions that day. Its own ICS advisory for the product had said on its November 18 revision that "no known public exploitation specifically targeting these vulnerabilities have been reported to CISA at this time." Seven days later the catalog said otherwise, and CISA has not published what it saw.
The three Danfoss CVEs and their federal deadlines
The AK-SM 800A is a store-management controller that supermarkets use to monitor refrigeration circuits and alarms. The listed entries are below; descriptions come from CISA's catalog data and the CVE records.
| CVE | What it allows | CISA due date |
|---|---|---|
| CVE-2023-25914 | Authenticated file read through the XML interface | Nov. 28, 2026 |
| CVE-2023-25915 | Authenticated command execution | Nov. 28, 2026 |
| CVE-2025-41450 | Unauthenticated web report with internal IPs, usernames, store names | Dec. 9, 2026 |

The 2023 pair affect versions before 3.3 according to the CVE records, published August 21, 2023. The 2025 flaw was fixed in release R4.2, per CISA's ICS advisory ICSA-25-140-03, which rates it 8.2 under CVSS 3.1 and 7.3 under CVSS 4.0.
How CVE-2025-41450 works: a code of the day
Claroty Team82's write-up describes a hidden path in the login flow. Two request attributes redirect authentication to a check_code_of_day routine, which checks a password derived from the device's current date rather than the administrator's own. The researchers reconstructed the algorithm, so anyone who reproduces it can generate a valid daily credential and get an administrative session. Claroty says the mechanism was "likely intended for vendor support or maintenance."
Tomer Goldschmidt of Claroty Team82 reported the flaws to CISA, per the advisory. CISA also notes that the flaws have high attack complexity.
Who can reach these controllers: 2,765 internet-facing devices
Claroty searched Shodan and Censys for the Danfoss StoreView web title. A Censys scan of AK-SM 800A devices returned 2,765 exposed units. The write-up does not say how duplicates or false positives were handled, so treat the figure as an upper-bound estimate of reachable interfaces.
With an administrative session, Claroty lists what an attacker can do through the management interface: monitor circuits, change temperature thresholds and operating schedules, clear or review alarms, change notification settings and manage users. It stops short of describing physical spoilage.
The score understates the 2023 pair
Both 2023 flaws need authentication, which usually lowers urgency. The score understates the combination: CVE-2025-41450 gives an unauthenticated path to usernames, and CVE-2023-25915 turns any valid login into command execution. CISA has not said whether the three were used together, and the catalog marks known ransomware use as "Unknown" for all three.
What operators should do
Danfoss's fix for CVE-2025-41450 is R4.2, and the later flaws CVE-2025-41451 and CVE-2025-41452 are fixed in R4.3.1, so R4.3.1 or later covers everything Claroty reported. CISA's guidance for the product is to keep it off the internet, behind a firewall and separate from business networks, with updated VPNs for remote access.
Anyone running AK-SM 800A units in a store should check whether the StoreView page answers from outside the network. CISA flagged forensic triage as required for the two 2023 entries, so organisations that find an exposed unit should preserve logs before updating. Earlier listings such as Mitel MiCollab and the Drupal installer flaws show the same pattern of a catalog entry arriving with a deadline measured in days. The next date to watch is December 9.
Sources
More in Security
- 01CERT-In Flags Five WhatsApp Flaws: The Fixed Builds and Who Can Exploit EachWhatsApp's own advisories list CVE-2026-102769, 44908, 23871, 23866 and 23863, and only the ad-reply bug carries a possible-abuse note.
- 02Java4Shell Needs AVX-512 Hardware and Java 17.0.6 or Later, Oracle and Calif Disagree on SeverityCVE-2026-114938 is a heap overwrite in the JVM's Base64 decoder; Oracle fixed it Nov. 17 and scored it 8.1, while the discoverer, Calif, scored it 9.2.